PROFIBUS, IO-Link, HART, M-Bus and Other Fieldbuses

Most fieldbuses are a UART or Manchester-coded serial stream on a physical layer built for long cables and electrical noise: RS-485, a current loop, a powered two-wire bus or a 24 V sensor cable. Once the signal is brought to logic levels, a logic analyser decoder can show the frames, addresses and data. This guide covers the fieldbuses that the ZeroPlus and Acute decoder libraries support. Modbus has its own guide.

PROFIBUS DPRS-485, 9.6 kbit/s to 12 Mbit/s
IO-Link24 V point to point, up to 230.4 kbaud
HART1200 bit/s FSK on a 4 to 20 mA loop
KNX TP9600 bit/s on a 30 V twisted pair
M-BusUtility meters, 300 to 9600 baud
SDI-121200 baud, one data wire, sensors

Where to Connect a Logic Analyser

A logic analyser reads logic levels, not the bus itself. On RS-485 buses (PROFIBUS DP) probe the receive and transmit pins of the transceiver, or use a differential probe on an oscilloscope. On HART, M-Bus, KNX and OpenTherm, probe the UART or logic side of the modem or interface chip. Connecting a logic probe straight to a 24 V, 30 V or 36 V bus can damage it, so check the probe's input range first.

PROFIBUS DP and PA

PROFIBUS DP runs on RS-485 at fixed rates from 9.6 kbit/s to 12 Mbit/s, using 11-bit UART characters: start bit, 8 data bits, even parity and stop bit. Telegrams start with one of four delimiters (SD1 0x10, SD2 0x68, SD3 0xA2, SD4 0xDC) or are a single 0xE5 short acknowledge. SD1, SD2 and SD3 telegrams end with 0x16, but the SD4 token telegram has no end delimiter. Stations have addresses 0 to 126, and a token passes between masters. PROFIBUS PA, used in process plants, runs at 31.25 kbit/s on the Manchester-coded, bus-powered MBP physical layer (IEC 61158-2) instead. The RS-485 guide covers termination and biasing, the usual cause of PROFIBUS faults.

IO-Link

IO-Link (IEC 61131-9) is a point-to-point link between an IO-Link master port and one sensor or actuator, over a standard unshielded 3-wire cable up to 20 m. Communication uses the C/Q line on pin 4 at 24 V levels, at one of three rates: COM1 4.8 kbaud, COM2 38.4 kbaud or COM3 230.4 kbaud, with 8 data bits and even parity. After a wake-up pulse from the master, the two exchange cyclic process data and on-request service data such as parameters and events. The same pin works as a plain switching input when IO-Link is not in use.

HART

HART adds digital data to a 4 to 20 mA analogue loop without disturbing the current reading. It uses Bell 202 frequency-shift keying: 1200 Hz for a 1 and 2200 Hz for a 0, at 1200 bit/s, as a small AC signal on top of the DC loop current. Bytes are sent with 8 data bits and odd parity. A logic analyser decodes HART from the UART side of a HART modem, after the FSK has been demodulated, not from the loop wires.

EtherCAT

EtherCAT is Ethernet-based: a master sends standard Ethernet frames that pass through every slave in turn, each reading and inserting its data on the fly. On the cable it is 100 Mbit/s Ethernet, far beyond a logic analyser's reach. ZeroPlus lists an EtherCAT decoder, which reads the MII signals between the EtherCAT controller and its PHY inside the device, not the cable.

KNX

KNX TP1, the twisted-pair form used in building automation, runs at 9600 bit/s on a bus that also supplies about 30 V DC to the devices. Each character is a start bit, 8 data bits, even parity and a stop bit, and every telegram is acknowledged. Telegrams carry source and destination addresses and group addresses that link switches to loads. Use the UART output of a KNX transceiver chip for decoding.

M-Bus (Meter-Bus)

M-Bus (EN 13757-2 and -3) reads water, heat, gas and electricity meters over a two-wire bus that can also power each meter's bus interface, and in some cases the meter itself. The master signals by changing the bus voltage (about 36 V for a 1, 24 V for a 0) and the meters reply by changing the current they draw. Data is sent at 300 to 9600 baud, 2400 being common, with 8 data bits and even parity. Frames are a single 0xE5 acknowledge, a short frame starting 0x10 or a long frame starting 0x68, and end with 0x16.

SDI-12

SDI-12 links environmental sensors such as soil moisture probes and weather stations to data loggers. It uses one data line plus ground and 12 V power, at 1200 baud with 7 data bits, even parity and 1 stop bit, and inverted logic: a 1 is near 0 V and a 0 is above 3.5 V. The logger wakes the sensors with a break of at least 12 ms, then sends a command such as 0M! to start a measurement at address 0. Set the decoder to inverted polarity.

OpenTherm

OpenTherm connects room thermostats to boilers over two polarity-free wires. The thermostat (master) signals by switching the line voltage and the boiler (slave) answers by switching the current. Each frame is 32 bits plus a start and stop bit, Manchester coded at 1000 bit/s: a parity bit, a 3-bit message type, 4 spare bits, an 8-bit data ID and a 16-bit value, such as the control setpoint. The master sends a request about once a second and the slave must reply within a set time.

How They Compare

BusPhysical LayerSpeedCharacter or Coding
PROFIBUS DPRS-4859.6 kbit/s to 12 Mbit/s8 data, even parity
PROFIBUS PAMBP, bus powered31.25 kbit/sManchester
IO-Link24 V C/Q line, point to point4.8, 38.4 or 230.4 kbaud8 data, even parity
HARTFSK on 4 to 20 mA loop1200 bit/s8 data, odd parity
EtherCAT100BASE-TX Ethernet100 Mbit/sEthernet frames
KNX TP130 V twisted pair, bus powered9600 bit/s8 data, even parity
M-BusVoltage and current modulation, bus powered300 to 9600 baud8 data, even parity
SDI-121 data wire, 12 V power1200 baud7 data, even parity, inverted
OpenTherm2 wires, voltage and current signalling1000 bit/sManchester, 32-bit frames

Common Faults and How to Find Them

SymptomLikely CauseWhat to Check
PROFIBUS errors rise with speedMissing or extra termination, stub lines too longCheck termination at both ends only; look at edge shape with an oscilloscope
IO-Link device falls back to SIOWake-up not answered, or cable too long or noisyCapture the wake-up pulse and the first frames on C/Q
HART device does not answerLoop resistance below the 230 ohm HART minimum (250 ohms is the usual value), or modem not keyedCheck the loop resistor and the modem RTS and data lines
M-Bus meters missing from a scanToo many meters or too much cable for the masterCheck bus voltage under load and the reply current
SDI-12 sensor ignores commandsBreak too short or decoder polarity wrongMeasure the break and confirm inverted logic

Tools for Decoding Fieldbuses

Watch tools capture the logic-level side of each bus and decode the frames. Coverage differs: ZeroPlus lists more fieldbus decoders, Acute lists PROFIBUS and M-Bus.

ProductRoleCapabilityPrice ex VAT
Acute TravelLogic 34-ChannelWatchAcute decoders for PROFIBUS and M-Bus, alongside Modbus and RS-485£1,260
ZeroPlus LAP-C Pro SeriesWatchZeroPlus decoders for PROFIBUS, IO-Link, HART, EtherCAT, KNX, SDI-12 and OpenTherm 2.2£925

Commissioning a mixed fieldbus plant? Tell us the buses and we will suggest probes and decoders.

Frequently Asked Questions

Can a Logic Analyser Connect Directly to PROFIBUS?

Not to the bus wires. PROFIBUS DP is differential RS-485; probe the transceiver's logic-side pins, or use an isolated differential probe on an oscilloscope.

What Is the Difference Between IO-Link and a Fieldbus?

IO-Link connects one device to one master port. The master then connects to a fieldbus or industrial Ethernet network. It replaces the last metre of wiring, not the network.

Why Does HART Need a Modem to Decode?

HART data is an FSK tone on top of the loop current. A HART modem converts the tones to a UART stream, which is what the decoder reads.

Is M-Bus the Same as Modbus?

No. M-Bus is a European standard for reading utility meters, with its own two-wire physical layer and frame format. Modbus is a general industrial protocol, usually on RS-485.

Which Decoder Settings Does SDI-12 Need?

1200 baud, 7 data bits, even parity, 1 stop bit and inverted polarity.