Converts RS-232C serial signals to RS-485 differential format for multidrop industrial networks.

SKU: 3313

Normaler Preis
€72,95 EUR exc tax
Normaler Preis Verkaufspreis
€72,95 EUR exc tax
Sale Ausverkauft
Versand wird beim Checkout berechnet
If no stock is shown above, order now and we'll dispatch within 10 working days.
Vollständige Details anzeigen

Key Features

RS-232 To RS-485 Conversion
Communication range up to 1200 metres
Optical isolation protection
Automatic transmit/receive switching
RS-485 Line Termination
Industrial temperature operation
Multidrop RS-485 network for Array instruments

Overview

The Array 3313 RS-232C to RS-485 Converter provides essential signal conversion for connecting PC systems to industrial RS-485 networks. Specifically designed for Array Electronic test equipment, this converter enables control of multiple electronic loads and power supplies from a single computer serial port.

The converter features optical isolation for protection against ground loops and electrical interference. Port-powered operation eliminates the need for external power supplies, whilst LED status indicators simplify installation and troubleshooting. The robust design supports industrial temperature ranges and provides reliable communication over distances up to 1200 metres.

Perfect for applications requiring remote control of programmable electronic loads, DC power supplies, and Array Electronic test equipment.

Downloads

Extended Communication Range

Enables control of remote instruments up to 1200 metres away from the PC

Multidrop Networking

Connects multiple Array Electronic devices using single twisted pair cable reducing wiring complexity

Plug-and-Play Operation

Port-powered design with automatic switching eliminates configuration complexity and external power requirements

Der Array Electronic 3313 RS-232C-zu-RS-485-Konverter verbindet die RS-232C-Signale mit RS-485-Differenzsignalen.

Der Konverter ist für den Anschluss eines PCs an ein Multi-Drop RS-485-Netzwerk zur Steuerung mehrerer elektronischer Array-Lasten und Stromversorgungen konzipiert.

Engineer Q&A

Questions and Answers

10 questions
  • How Do I Configure Device Addresses on the Network?

    Set each instrument's address on its front panel: press Menu and select Address Set (364X) or Address (371X). Addresses run from 0 to 31 on 364X supplies and 0 to 254 on 371X loads; give each instrument a unique address.

    Answered by John LeggUpdated 8 Oct 2026
  • What Baud Rates Are Supported?

    Array does not publish the converter's own baud range. The 364X and 371X instruments support 4800, 9600, 19200 and 38400 baud. Lower speeds are generally more reliable over long cable runs.

    Answered by John LeggUpdated 8 Oct 2026
  • Can I Use the 3313 with Non-Array Equipment?

    Array lists the 3313 only as an accessory for its own instruments and does not state compatibility with other RS-485 devices. It may work with other equipment using the same RS-485 wiring, but match the communication parameters and addressing, and test it before relying on it.

    Answered by John LeggUpdated 8 Oct 2026
  • How Do I Troubleshoot Communication Problems?

    Check that termination resistors are installed at the network ends. Check RS-485 polarity (A to A, B to B), and make sure every instrument has a unique address and the same baud rate as the software.

    Answered by John LeggUpdated 8 Oct 2026
  • Is the 3313 Isolated?

    Yes. Array describes the 3313 as an isolated RS-232 to RS-485 adaptor, which helps prevent ground loops. Array does not publish the isolation type or rating, or any other protection features.

    Answered by John LeggUpdated 8 Oct 2026
  • What Array Electronic Devices Are Compatible with the 3313 Converter?

    The 3313 is designed for Array electronic loads and power supplies in the 364X and 371X series, including the 3710A/3711A electronic loads and 3644A/3645A/3646A power supplies. Each device needs a unique address for multidrop operation.

    Answered by John LeggUpdated 8 Oct 2026
  • How Many Devices Can Be Connected to a Single 3313 Converter?

    Array does not state a maximum. Standard RS-485 allows 32 unit loads on one segment. Each instrument needs a unique address, set on its front panel: 0 to 31 on 364X supplies and 0 to 254 on 371X loads.

    Answered by John LeggUpdated 8 Oct 2026
  • What Cable Type Should I Use for RS-485 Connections?

    Use twisted pair cable with 120Ω characteristic impedance. Install 120Ω termination resistors at both network ends. For distances over 100 metres, use shielded twisted pair cable with proper grounding.

    Answered by John LeggUpdated 8 Oct 2026
  • Does the 3313 Require External Power?

    Array's wiring diagram shows a +5V supply pair on the bus cable to the instruments, but Array does not state how the 3313 itself is powered. Check the diagram before installation, or ask us.

    Answered by John LeggUpdated 8 Oct 2026
  • What Is the Maximum Communication Distance?

    Array does not publish a maximum distance. The RS-485 standard allows up to about 1200 metres (4000 feet) at lower baud rates, and higher speeds need shorter cables. A common rule of thumb is speed × distance ≤ 10^8 bit/s × metres.

    Answered by John LeggUpdated 8 Oct 2026